The following table is a summary of two separate - before and after - tests, on an oily water separator system in Cape Town. The first test was done on the 12th May 2009, and the follow up test on the 8th June 2009.

 

These tests were conducted by an independent laboratory - a division of Eskom. We have copies of the original documentation for those who wish to see them. We are also happy to arrange for you to use this or any other laboratory of your choice for testing your own site effluent or the site of spillage.

 

The test results were given the following remarks:

  • Before test - Water of this quality is unsuitable for discharge into a sewer. COD exceeds the limit. Oil / sludge traps should be cleaned on a regular basis.
  • After test - Water of this quality is acceptable for discharge into a sewer. 

Test Results Table
------------------------

 Analyte

 Value Before
Value After
 Unit Minimum Maximum Method
 Cadmium <0.005 <0.005 mg/l Cd
  5 Eskom No 412
 Chromium 0.1 0.01 mg/l Cr
  10 Eskom No 412
 COD 8740 683 mg/l O2
  5000 HACH P 2/218
 Colour Turbid Turbid    
 Conductivity 206 39 mS/m @25 C
  500 SABS 1057
 Copper 2.9 0.63 mg/l Cu
  20 Eskom No 412
 Fat, Grease & Oil
 197 7.7 mg/l  400 SABS 1051
 Iron 16 2.3 mg/l Fe
  50 Eskom No 412
 Lead 1.3 0.18 mg/l Pb
  5 Eskom No 412
 pH
 7.0 6.4 @25 C
 5.5 12 SABS 11
 Suspended Solid
 263 44 mg/l  1000 SABS 1049
 Zinc 16 1.1 mg/l Zn
  30 Eskom No 412
 